General
Topology
On-line double conversion with PFC (Power Factor Correction) system
Configuration
Rack/Tower
Part Number
9PX11KiPM31 + 9PXEBM240
Rating (VA/Watts)
11000/10000
Dimensions (H x W x D, mm)
440 x 260 x 700
Weight (kg)
88
Electrical Input
Connection
Hardwired - see manual for terminal block layout
Input Voltage Range
305V-480V without derating (up to 175V-480V with derating)
Nominal Voltage
380/400/415V
Frequency
50/60 Hz autoselection
Frequency Range
40-70 Hz
Short Circuit Current
150 A
THDI
<5%
Electrical Output
Voltages
200/208/220/230/240/250V +/- 1%
Voltage THD
< 2%
Output Receptacles
Hardwired - see manual for terminal block layout
Overload Capacity
102-110% : 120s, 110-125%: 60s, 125-150%: 10s, >150%: 900ms
Efficiency (Normal Mode)
Up to 95% in Online mode, 98% in Hi-Efficiency mode
Output Frequency
50/60 Hz autoselect, frequency converter as standard
Battery
Battery Management
ABM� and Temperature compensated charging method (user selectable),
automatic battery test, deep discharge protection, automatic
recognition of external battery units.
Extended Battery Capability
EBM (3U)
Communications
User Interface
Multilingual graphical LCD display
Communication Ports
1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used
simultaneously), 4 dry contacts (DB9), 1 mini terminal block for
remote On/Off and 1 for remote power Off, 1 DB15 for parallel
operation
Communication Slot
1 slot for Network-MS card, ModBus-MS or Relay-MS cards.
Environmental & Standards
Audible Noise
<50dB
Operating Temperature
0 to 40�C continuous
Safety markings
IEC/EN 62040-1, CSA 22.2
EMC Markings
IEC/EN 62040 -2 , IEC/EN 62040-3 (Performance)
Approvals
CE, CB report (TUV), C-Tick